C118 Digital Expansion Module

Budget-friendly price Request a quote
16 opto-isolated inputs | 16 open collector outputs | Max. 1000Vdc / 50Vdc | For TMF500 datalogger | DIN rail | 10.8 ÷ 15Vdc

The NESA C118 module is a digital channel expansion unit for the TMF500 terminal, featuring 16 opto-isolated digital inputs (max. 1000Vdc) for ON/OFF states and 16 open collector outputs (max. 50Vdc, 200mA). It connects to the TMF500 unit via PS/2 cables and is configured through a web page.

The TMF500 allows you to manage a total of 32 individually configurable digital I/Os. It supports up to three C118 expansion units, for a total of 96 digital I/Os. It is powered by 10.8–15Vdc from the datalogger and consumes less than 10mA @ 12Vdc; the input connectors are gold-plated and it is DIN rail mountable.

Key points

  • 16 opto-isolated digital inputs for ON/OFF states (max. 1000Vdc)
  • 16 open collector outputs (max. 50Vdc, 200mA)
  • LEDs for displaying statuses and commands; gold-plated input connectors
  • Power supply 10.8 ÷ 15Vdc from the TMF500 datalogger; consumption < 10mA @ 12Vdc
  • PS2 cable connection; web page configuration; DIN rail
  • 32 digital I/O per module; up to three C118s per TMF500, 96 digital I/Os in total
  • Input pins: GND, In_1 to In_4, Vcc; Output pins: GND, Out_1 to Out_4, Vcc

Technical Frequently Asked Questions

What voltages does it support?

Inputs: max. 1000Vdc. Open collector outputs: max. 50Vdc, 200mA.

How many modules does the TMF500 support?

Up to three C118 expansions, for a total of 96 digital I/O. Each module adds 32 individually manageable and configurable digital I/O.

How does it connect to the TMF500?

Via PS2 cables. It is configured from a web page.

Properties

FeatureSpecification
Entrances and exits
Product typeDigital expansion module
FunctionExpansion of the digital channels of the TMF500 terminal
Digital tickets16
Ticket TypesOpto-isolated, for ON/OFF states
Maximum input voltage1000Vdc
Departures16
Type of outputsOpen collector
Maximum output voltage50Vdc
Maximum output current200mA
SignalingLED for displaying statuses and commands
Input connectorsGolden
Power, connection and link
Feeding10.8 ÷ 15Vdc, from the TMF500 datalogger
Consumption< 10mA @ 12Vdc
DataloggerTMF500
Connection cablePS2
ConfigurationFrom website
Digital I/O managed by the TMF500 with a module32, manageable and configurable separately
C118 modules by TMF500Up to three
Digital I/O with three modules96
FixationDIN rail
NESA C118 Digital Expansion Module
Dimensions of the NESA C118 digital expansion module

Other products

Official logo of Novotechnik, manufacturer of linear sensors, position transducers, and industrial encoders
Output 0…10 V, 0…20 mA or 4…20 mA | Power supply 24 VDC ± 20 % | Linearity typ. 0.01 %FS | 20 ppm/K typ. | Reference 10 VDC for sensor | DIN rail 35 mm | Galvanic isolation (MUP-160)
NESA Environmental Meters
Thermopile (output in mV) | -2000 ÷ +2000 W/m² | <±5% on standard terrain | 50 µV/(W/m²) | ISO8302 · CE | <200 g
NESA Environmental Meters
RS485 | Water film 0–4 mm | Dry / Damp / Wet / Ice / Snow | IP68 | -30–+70°C | 120 x 50 mm
NESA Environmental Meters
4÷20mA / ModBus RS485 | NO2 | 0÷20 / 0÷200 ppm | -30 ÷ 50°C | 11…30 Vdc | IP54 | 230g
DPF Sensors logo
Rotation and sub-speed control relay to detect absence of movement, slippage, belt breakage and jams in industrial machinery.
NESA Environmental Meters
O3 and VOC | 0÷0.15 / 0÷0.5 / 0÷10 ppm (O3) | 0÷25 / 0÷500 ppm (VOC) | LCD 3.5 figures | 0÷5V DC or RS485 / ModBus | 12V DC, 800mA | 130x94x57mm
NESA Environmental Meters
K-band radar <25GHz | 0÷20 m | 0.01% fs (±2 mm) | 4÷20mA | Current loop or 10÷28 Vdc | IP66 – IP68 (0.2 bar) | 285 x 72 mm
Dimetix_AG-1
High-Speed Communication (500 Hz / 2 ms) with IP65 Industrial Protection: Synchronous Real-Time Data Transfer for Critical Processes
Monitran-Logo
IEPE Portable Vibration Meter for Accelerometers | ISO 10816-3 | 20 g, 200 mm/s, 2000 µm | RMS, Peak, Peak-to-Peak, Crest Factor | 100 Memories | 160 x 128 TFT Display | >20 h Lithium-ion Battery
Shopping Basket