MCS Signal Conditioning Module

Budget-friendly price Request a quote
Single-channel | Inputs: Pt100, thermopile, voltage, current, frequency | Outputs: 0-2Vdc, 0-20mA, 4-20mA, RS485, Modbus | 18-bit | 10-30Vdc

The NESA MCS is a single-channel module for conditioning digital and analog electrical signals. It accepts Pt100 signals, thermopiles, voltages up to 2Vdc (or micro-voltages, e.g., 0-100mV), currents 0-20mA or 4-20mA, frequencies up to 1000Hz, and pulse counts (min. 1ms) as inputs, and generates a standardized signal in 0-2Vdc voltage, 0-20mA or 4-20mA current, RS485 digital format, or Modbus over RS485.

It converts 18 bits (over 262,000 points) onto a differential input with <2µV accuracy across the entire scale. It operates on 10–30Vdc, typically consumes 4mA @ 12Vdc, and functions from -40°C to +80°C. This 2-unit DIN rail module complies with CE standards. It is programmable via a USB-MCS-I interface.

Key points

  • Inputs: Pt100, thermopiles, voltages up to 2Vdc, currents 0÷20mA or 4÷20mA, frequency up to 1000Hz and pulse count (min. 1ms)
  • Outputs: 0-2Vdc, 0-20mA, 4-20mA, RS485 and Modbus over RS485
  • 18-bit resolution with over 262,000 points; accuracy <2µV across the entire scale
  • Power supply 10÷30Vdc; typical consumption 4mA@12Vdc; -40°C÷+80°C
  • Any input can be associated with any output, with zero and offset regulation
  • DIN rail module, 2 units; compliant with CE standards

Technical Frequently Asked Questions

What is MCS?

A single-channel module for conditioning digital and analog electrical signals, which generates a standardized signal in voltage, current, RS485 or Modbus over RS485.

What signals does it accept at input?

Pt100, thermopiles, voltages up to 2Vdc (or micro voltages, e.g. 0÷100mV), currents 0÷20mA or 4÷20mA, frequency up to 1000Hz and pulse count (min. 1ms).

What options does it offer?

Voltage 0÷2Vdc, current 0÷20mA or 4÷20mA, RS485 (via command line) and Modbus over RS485. The RS485 is not isolated.

What is its resolution and accuracy?

18-bit resolution with over 262,000 points; accuracy <2µV across the entire scale.

How is it programmed?

With the USB-MCS-I interface, a USB/485 converter with included software that defines the linearization line with zero and offset.

What is the reference?

MCS: DIN rail module. The selected input and output types are indicated.

Properties

FeatureSpecification
Inputs and accuracy
Product typeSingle-channel module for conditioning digital and analog electrical signals
Differential inputWith current generator for Pt100
Temperature inputPt100, thermopiles
Power inputVoltages up to 2Vdc (micro voltages, e.g. 0÷100mV)
Power input0÷20mA or 4÷20mA
Frequency inputUp to 1000Hz
Pulse countMin. 1ms
Resolution18-bit with more than 262,000 points
Accuracy<2µV across the entire scale
Departures
Voltage output0÷2Vdc
Current output0÷20mA or 4÷20mA
Digital outputRS485 (via command line)
Modbus outputModbus over RS485
Real-time readingWith digital output, input signal values are sent directly to the RS485 line (not isolated)
Functions and programming
ProgrammingUSB-MCS-I Interface
SelectionInputs on different scales and outputs, with the possibility of associating different measurement scale ranges
RegulationZero and offset
Input-output associationOnce the electrical range and the type (analog or digital) of the input are defined, a standard output is chosen and a specific measurement range is associated with it.
ExamplePt100 signals with different ranges (e.g. -40°C to +60°C and 0 to +80°C) associated with the same output (e.g. 0 to 2Vdc), or the same input signal with different outputs
«Analog» counting systems»Automatic reset when the imposed bottom-of-scale value is exceeded
SupplyCalibrated with extremely high precision systems and programmed according to the customer's specifications
Power supply, environment, and mechanical data
Feeding10÷30Vdc
ConsumptionTypical 4mA@12Vdc
Operating temperature-40°C to +80°C
ContainerModule for DIN rail, 2 units
AccordanceEC
ReferenceConfiguration
MCSMCSDescription: DIN rail module, pre-programmed for the conversion of input signals: Pt100, thermopile, voltages (micro-voltages 0-100mV) and currents or digital signals (frequency or count), and output signals: 0-2Vdc, 0-20mA, 4-20mA, RS485, Modbus RTU RS485. The selected input and output types are indicated.
NESA MCS Signal Conditioning Module

Other products

Monitran-Logo
Sensor and Cable Tester | Bias Voltage Diagnostics | Tri-Color LED Status | BNC Input | 9V Battery Powered | Portable and Ergonomic | Short Circuit Identification | Open Loop Verification | Field Tool | ABS Housing
DPF Sensors logo
Isolated multiplexer with 4 Pt100 probes, obtaining double output (0-4/20mA and 0/10V)
DPF Sensors logo
Three-phase network analyzer with indication, RS485 + 4/20mA, 3 x /5A input – 3 x 550VAC
NESA Environmental Meters
Pt100 inputs, voltage, current, frequency | 18-bit | SigFox, LoRa/NESA, SMS | 860 ÷ 920MHz | -40 ÷ +60°C | IP65 | 225 x 300 x 50 mm
Official logo of Novotechnik, manufacturer of linear sensors, position transducers, and industrial encoders
Output 0 … 10 V, ±10 V, 0 … 20 mA or 4 … 20 mA | Input > 10 MΩ | 18 … 30 VDC | Housing 64 x 58 mm, IP 66 | -25 … +70 °C
DPF Sensors logo
General purpose power supply, with 75W / 120W / 240W power, 24 Vdc output
DPF Sensors logo
Universal 2-way galvanic converter/isolator. Input: 0…500 mV, 0…700 V, (solar spatial up to 1500 V) / 20 mA, PWM. Multiple output: 0/10 V (0/5 V DC) and 0-4/20 mA.
DPF Sensors logo
High-precision AC/DC (TRMS) current transformer to 4/20mA current loop, with isolation. 0/150A – 0/300A – -150/+150A – -300/+300A
NESA Environmental Meters
0-1Vdc, 4-20mA, RS485/Modbus | 0-100% RH | Thin-film capacitive | 26 x 220 mm | 10-30Vdc | Weight < 80 g
Shopping Basket