Installation of conductive level sensors: electrodes and cables

Installation of conductive level sensors: electrodes and cables

Technical guide · GUEMISA

Conductive levelCommon electrodeShielded cableBraided pair with meshdoctec_002-c Rev. 00
Quick responseA conductive level sensor measures the electrical resistance of the medium between electrodes and transmits it to the level relay. Four points must be considered during installation: electrode placement (especially the common electrode), probe-to-relay distance, cable type and proximity of electromagnetic interference. The maximum probe-relay distance can exceed 1000 meters or fail below 3 meters.

Principle and factors of the installation

The conductive level control system is based on measuring the electrical resistance of the medium being monitored. Electrodes in contact with the medium collect this information by closing the electrical circuit between them and transmit it to the level relay, which then operates according to its operating mode.

Proper functioning depends on factors that may be related to each other:

  • The type of deposit
  • The resistivity/conductivity of the medium to be controlled
  • The location of the electrodes in the tank
  • The type of cable and its length
  • Installing the cable from the sensor to the relay
  • Electromagnetic interference that may be radiated by external elements

The guide assumes that the type of sensor has been chosen according to the mechanical characteristics and access to the tank, and that the relay fulfills the required level control function.

Common or reference electrode

The resistivity reading of the medium is always taken between the common electrode and the other electrodes. Therefore, it must always be in contact with the medium: it is installed at the lowest point of the tank or immediately below the electrode that monitors the lowest point (minimum level or low level alarm).

Ideally, it should be as close as possible to the other electrodes. The greater the distance between the common electrode and the others:

  • The higher the resistivity being measured, the further it may fall from the relay's measurement range. Different relays are available for different resistivity ranges.
  • Greater sensitivity to disturbances radiated by electromagnetic interference, which can cause unexpected effects on the level relay.

If the tank is metallic, it can be used as a common electrode because the medium is always in contact with it. It is advisable that the other electrodes be placed as close as possible to the tank walls.

DepositCorrect installationInstallation not recommended
Any typeThe electrodes remain close to each other.The electrodes remain away from the common electrode
MetalThe electrodes remain close to the common electrode, which is the tank wall.The electrodes remain away from the common electrode, which is the tank wall.
Correct installation: electrodes close together
Correct installation: electrodes close together
Installation not recommended: electrodes far from the common electrode
Installation not recommended: electrodes far from the common electrode

Recommended cable types

Cables can be crucial for proper operation. It's not essential to always use the highest-quality cable; it must be suitable for the distance, pumping equipment, and electromagnetic interference conditions of the installation. The recommended cross-section depends on the type of cable; the longer the cable, the larger the cross-section.

WireSectionImmunity against electromagnetic disturbancesConnection
Standard1..2.5 mm²NullEach cable to the corresponding electrode. For installations without special conditions.
Screened1..1.5 mm²ModerateEach wire connects to its corresponding electrode. Connect the shield to ground at one end, preferably on the relay side. If the ground connection is unreliable, it's best not to connect the shield.
Braided pair with mesh0.52 mm²ElderlyConnect one wire from each pair to the common electrode. Connect the shield to ground at one end, preferably on the relay side. If the ground is unreliable, it's best to leave the shield unconnected.
Installation with shielded twisted pair cable
Installation with shielded twisted pair cable
Installation with shielded cable
Installation with shielded cable
Installation with standard cable
Installation with standard cable

Probe cables and power cables

  • It is highly advisable that the probe cable not run in parallel with other power or inductive control cables (solenoid valves, motors, etc.).
  • If they have to be installed in parallel, the distance between them should be as great as possible.
  • The probe cable can be crossed with the power cables without any problem.
Maximum separation between probe cables and power cables
Maximum separation between probe cables and power cables
Avoid parallel installation and short distances
Avoid parallel installation and short distances
The probe cables and the power cables can be crossed without any problem.
The probe cables and the power cables can be crossed without any problem.

Maximum distance between probes and relay

The maximum distance between the probes and the relay depends on all the factors mentioned above. It could exceed 1000 meters with optimal operation, or it might not function at a distance of less than 3 meters, so these factors must be taken into account when planning the installation.

Frequently Asked Questions

Where is the common electrode installed?

At the lowest part of the tank or immediately below the electrode that controls the lowest point (minimum level or minimum level alarm), so that it is always in contact with the medium.

Can a metallic deposit be used as a common electrode?

Yes. The medium is always in contact with the tank. It is recommended that the remaining electrodes be as close as possible to the walls.

Which cable offers the most immunity to interference?

The twisted pair with mesh (0.52 mm² cross-section). The shielded version offers moderate immunity, and the standard version offers none.

How is the cable mesh connected?

Connect the electrical ground to one end only, preferably the relay side. If the electrical ground is unreliable, it's best not to connect it.

Can the probe cables run alongside the power cables?

It is advisable to avoid running them in parallel with power or inductive control cables; if this is unavoidable, maintain the maximum possible distance. They can be crossed without any problem.

What is the maximum distance between the probe and the relay?

It depends on the installation factors: it could exceed 1000 meters with optimal operation or not work at a distance of less than 3 meters.

Related

Below, the original PDF document is available for viewing or downloading.

Shopping Basket