Signal conditioner for potentiometers MUP-080

Budget-friendly price Request a quote
Potentiometer input 0.5…100 kΩ | Output 0…10 V or 4…20 mA | Power supply 18…30 VDC | Typical linearity 0.1 % | Temperature coefficient 25 ppm/°C | DIN rail 35 mm | IP20

Novotechnik MUP-080 signal conditioner. It powers the potentiometer and delivers a proportional, normalized signal.

Analog signal conditioner for linear and rotary potentiometers, basic version with fixed amplification. Potentiometer input 0.5…100 kΩ; output 0…10 V or 4…20 mA. Typical linearity 0.1%, response time 1 ms. For 35 mm DIN rail mounting.

Key points

  • Standardized output signals 0…10 V or 4…20 mA
  • Temperature coefficient 25 ppm/°C
  • Power supply 18…30 VDC; supports unstabilized power supplies

Technical Frequently Asked Questions

What sensors and signals can be connected to the MUP-080 signal conditioner?

Accepts sensor: linear or rotary potentiometer; input signal: cursor signal, 0%…100%; signal pickup: almost no load; permissible potentiometer resistance: 0.5…100 kΩ; internal reference voltage for potentiometer: 10 VDC, ±0.2%.

How do I order the MUP-080 signal conditioner?

The order code has four fields: type, power supply, input, and output. For example, MUP-080-111 (Art. 400054220) is the version with an uninsulated power supply, input 0% to 100%, and output 0 to 10 V. The reference table on this page lists all order references with their corresponding Art.

Under what conditions does the MUP-080 signal conditioner operate?

Operating temperature: -20…+60 °C. Protection: IP20 (NEMA 1).

Properties

FeatureSpecification
Entrance
SensorLinear or rotary potentiometer
Input signalCursor signal, 0%…100%
Signal pickupAlmost no load
Potentiometer allowable resistance0.5…100 kΩ
Internal reference voltage for the potentiometer10 VDC, ±0.2%
Extent
Linearitytyp. 0.1%
Gain tolerance1 %
Offset tolerance1 %
Precision±1 % of the range
Overload capacity10x (t < 30 ms); 2x
Calibrationat 23 °C and 40% relative humidity
Temperature coefficient25 ppm/°C
Response time1 ms
Stabilization time15 min
What delivers
Output versions0…10 V or 4…20 mA (depending on the reference)
GuyFixed amplification
Current output load≤ 500 Ω
Maximum load of the voltage output1 kΩ
Non-linearity of the output0.15% of the range
Curly5 mV residual ripple with 10 V input signal
Feeding
Supply voltage18…30 VDC
Feed relative to outputWithout galvanic isolation
Current consumptionmax. 30 mA
Powermax. 2.5 W
Reverse polarity protectionYes, on the power lines
Dielectric strength1.5 kV for 1 min between power supply and input/output
IsolationPollution degree II, measurement category III; power supply > 550 V (ZI), 255 V (DI)
Environment and rules
ProtectionIP20 (NEMA 1)
Working temperature-20…+60 °C
Storage temperature-20…+85 °C
EMCEN 61326-1
Electrical safetyEN 61010-1, A2
Mechanical data
Dimensions90.5 x 79 x 25 mm
Housing materialPA 66S, non-flammable according to UL94V-0, green
Fixation35 mm DIN rail (DIN EN 50022)
ConnectionTerminal block, up to 1.5 mm² (AWG 14)
Accordance
EU: Low voltageDirective 2014/35/EU: EN 61010-1
EU: Electromagnetic compatibilityDirective 2014/30/EU: EN 61326-1
EU: RoHSDirectives 2011/65/EU and 2015/863/EU: EN IEC 63000:2018
United Kingdom: Electrical safetySI 2016/1101: EN 61010-1
United Kingdom: Electromagnetic compatibilitySI 2016/1091: EN 61326-1
United Kingdom: RoHSSI 2012/3032 and SI 2020/1647: EN IEC 63000:2018
ReferenceConfiguration
MUP-080-111MUP080111Art. 400054220 · Output: 0…10 V
MUP-080-113MUP080113Art. 400054221 · Output: 4…20 mA
Novotechnik MUP-080 Signal Conditioner for Potentiometers
Dimensional drawing Signal conditioner for potentiometers MUP-080 Novotechnik

Other products

DPF Sensors logo
Extension of 4 or 8 Pt100 probes for the MUX8Pt-ISO
Monitran-Logo
19″ 3U Rack Architecture | Capacity: 12 Modules + Display | 64-Way DIN 41612 Connectors | Universal Power Supply 85-264V AC | Optional 12V/24V DC Power Supply | Configurable Relay Outputs | Modbus RTU/TCP | Data Logging Per Channel | Optional IP65 Enclosure | Industry Standard Certification
DPF Sensors logo
High-precision AC/DC (TRMS) current transformer to 4/20mA current loop, with isolation. 0/150A – 0/300A – -150/+150A – -300/+300A
DPF Sensors logo
AC/DC to RS485 Modbus + 0/10V current transformer, with isolation, high precision, up to 300 amps.
Digital pressure gauge
DPF Sensors logo
Voltage monitoring relay (VDC). Overvoltage and undervoltage
DPF Sensors logo
STOPWATCH indicator, 32 x 74 format. Simple or cyclic timer. Precision timer
DPF Sensors logo
Isolate 4/20mA or 0/20mA signals, 2 channels, do not need auxiliary power supply, they are placed as a simple transformer, double
DPF Sensors logo
Generator – simulator of PROCESS electrical signals.
DPF Sensors logo
RS232 – RS485 – RS232 Isolator-Repeater Converter
Shopping Basket