Signal conditioner for potentiometers MUP-410

Potentiometer > 500 Ω | 4…20 mA, 0…10 V, ±10 V | 24-bit Sigma-Delta | Up to 7.2 kHz | 10…30 VDC/24 VAC | 35 mm DIN rail

Novotechnik MUP-410 signal conditioner. DIN rail signal converter.

Convertidor de señal con microprocesador para potenciómetros (> 500 Ω). Conversión A/D Sigma-Delta de 24 bit, frecuencia de medición hasta 7,2 kHz. Salida normalizada 0…2/5/10 V, ±10 V, 4…20 mA o 0…5/20 mA, precisión de salida ±0,02 %FS. Ajuste Teach-In con 2 pulsadores frontales; el rango de entrada se puede limitar hasta el 80 % del rango total.

Key points

  • Input for potentiometric position sensors with resistance > 500 Ω
  • Standard outputs 0…2/5/10 V, ±10 V, 4…20 mA and 0…5/20 mA
  • 24-bit Sigma-Delta converter with a measurement frequency of up to 7.2 kHz
  • Galvanic isolation using DC/DC transformers
  • Teach-In with 2 front pushbuttons and tare function
  • Signaling of overtaking due to exceeding or falling short of the learned range
  • Typical temperature drift < 15 ppm/K

Technical Frequently Asked Questions

What sensors and signals can be connected to the MUP-410 signal conditioner?

Admite tipo de entrada: potenciómetro (1 entrada); resistencia admisible del potenciómetro: > 500 Ω; alimentación del potenciómetro: 2,5 VDC / 5 mA; etapa de entrada: lectura sin carga; bornes de la entrada: 7, 8, 9; entradas externas: 2 (Ext. 1 y Ext. 2), por contacto libre de tensión; sobrecarga: 10x (t < 30 ms), 2x.

How do I order the MUP-410 signal conditioner?

For example, MUP-410-11 (Art. 400108799) is the version with a default output of 4…20 mA, configurable with DIP microswitches. All the options for each field are available in the order code configurator on this page.

Under what conditions does the MUP-410 signal conditioner operate?

Operating temperature: -20…+60 °C. Protection: IP20.

Properties

FeatureSpecification
Entrance
Entry typePotentiometer (1 input)
Potentiometer allowable resistance> 500 Ω
Power supply for the potentiometer2.5 VDC / 5 mA
Entry stageLectura sin carga
Entrance terminals7, 8, 9
External inputs2 (Ext. 1 and Ext. 2), by voltage-free contact
Overload10x (t < 30 ms), 2x
Mechanical data
Dimensions90.5 x 79 x 25 mm
HousingPA66 green, non-flammable UL 94 V-0
Fixation35 mm rail (DIN EN 60715)
Connection1.5 mm² (AWG 14) screw terminals
Terminal section indicated in the manual0.05…2.5 mm² (AWG 30…12)
Mechanical resistanceEN 60068-2-6 ed. 2:2008
Seismic qualificationIEC/IEEE 60980-344 Ed. 1.0, 2020, paras. 6 and 9
Extent
A/D Converter24-bit Sigma-Delta with PGA
Measurement frequency100…7 200 measurements/s (7 200 by default)
Latency< 580 µs
Response time< 160 µs
Input accuracy±0.01 %FS
Output accuracy±0.02 %FS
Output accuracy (0…5 V)±0.03 %FS
Output accuracy (0…2 V)±0.05 %FS
Output accuracy (0…5 mA)±0.05 %FS
Nonlinearity0.024 %FS
Inlet temperature coefficient15 ppm/°C
Outlet temperature coefficient15 ppm/°C
Typical temperature drift< 15 ppm/K
Teach-In Resolution16 bit
Exit
Guy1 isolated output, 16-bit DAC
Power output4…20 mA (default), 0…5 mA, 0…20 mA, 20…4 mA
Load at current output< 500 Ω / 12 V
Voltage output0…2 V, 0…5 V, 0…10 V, ±10 V
Load at voltage output≥ 1 kΩ
Power output terminals3, 4
Voltage output terminals3, 5
Digital interfacesAvailable upon request: RS485, Modbus, USB
Sensor wire breakage output
configured outputWith sensor wire breakage
0…2 Vapprox. 2.2 V
0…5 Vapprox. 5.5 V
0…10 Vapprox. 11 V
±10 Vapprox. 11 V
0…5 mAapprox. 5.5 mA
0…20 mAapprox. 22 mA
4…20 mAapprox. 3.2 mA
20…4 mAapprox. 3.2 mA
Functions
Teach-InAdjust the input range using the Hi and Lo pushbuttons.
TareWith the Hi push button or with the external input Ext. 2
Overtaking signalExcess or deficiency of the learned range
ConfigurationOutput and measurement frequency with DIP microswitches
Pushbutton lockWith external input Ext. 1 (terminals 12 and 14 connected) or with DIP 2
IndicationRGB status LED
WatchdogRestart after 500 ms
With OMNI Link, on request (microUSB)Operation, adjustment and upgrade of the equipment
Mathematical functions (only with OMNI Link)Polynomial, inverse polynomial, logarithm, exponential, power, root
Linearization (only with OMNI Link)Linear interpolation at 100 points
Digital filters (only with OMNI Link)Exponential, floating-point, arithmetic mean, and rounding
Simulation (only with OMNI Link)Yeah
Food and environment
Feeding10…30 VDC/24 VAC, ±10 %
Consumption2.5 VA
Power factorPF ≥ 0.4
Starting currentISTP < 40 A/1 ms
Isolated feedingYeah
Power terminals1 (power +), 2 (GND power)
FuseInternal T500 mA
Galvanic isolationDC/DC Transformers
Dielectric strength2.5 kVAC, 1 min, between power supply and signal input
2.5 kVAC, 1 min, between signal input and outputs
ProtectionIP20
Safety classI
Insulation resistance (contamination degree II, measurement category III)Power supply: > 300 V (PI), 255 V (DI); input/outputs: > 300 V (PI)
Stabilization period5 minutes after switching on
CalibrationAt 25 °C and 40 % hr.
Working temperature-20…+60 °C
Storage temperature-20…+85 °C
Working humidity< 95 % hr, non-condensing
EMCEN 61326-1 (industrial environment)
Electrical safetyEN 61010-1, A2
RoHSEN IEC 63000:2018
Accordance
EU: Electromagnetic compatibilityDirective 2014/30/EU: EN 61326-1
EU: Low voltageDirective 2014/35/EU: EN 61010-1
EU: RoHSDirectives 2011/65/EU and 2015/863/EU: EN IEC 63000:2018
United Kingdom: Electromagnetic compatibilitySI 2016/1091: EN 61326-1
United Kingdom: Electrical safetySI 2016/1101: EN 61010-1
United Kingdom: RoHSSI 2012/3032 and SI 2020/1647: EN IEC 63000:2018
OptionMeaning
Example: MUP-410-11 (Art. 400108799) = 4…20 mA output by default, configurable with DIP microswitches.
3 · Configuration
114…20 mA (default), P/N 400108799. Configurable with DIP switches: 0…2/5/10 V, ±10 V, 0…5/20 mA
The code is formed using one option from each field, in the order shown in the example. Contact us and we will confirm the exact reference.
ReferenceConfiguration
MUP-410-11MUP41011Art. 400108799 · Factory setting: 4…20 mA, 7200 measurements/s
Novotechnik MUP-410 Potentiometer Signal Conditioner
Dimensional drawing of the Novotechnik MUP-410-11 signal conditioner with measurements for mounting on DIN rail.

Other products

Solid State Relay (AC) 32A with Radiator Rail
Isolated pulse frequency converter (0.01 to 100 KHz)
Official logo of Novotechnik, manufacturer of linear sensors, position transducers, and industrial encoders
Magnetostrictive | IO-Link V1.1, COM 3 | Stroke 50 … 4250 mm | Resolution 1 or 5 µm | 1 to 3 position markers | 18 … 30 VDC | 350 bar · IP67 / IP68
16-channel 0-4/20mA statically switched multiplexer
Compact 4G GPS tracker with Bluetooth, internal battery and inputs/outputs for basic vehicle and fleet tracking.
4/20mA signal isolator duplicator, *** INPUT: ACTIVE/PASSIVE *** OUTPUTS: 2X 4/20mA active, 24VDC (20.. 30V) isolated
Process relay v/i. Digital setpoint with numerical preselectors
Official logo of Novotechnik, manufacturer of linear sensors, position transducers, and industrial encoders
Output 0 … 10 V or 4 … 20 mA | Profile 18 x 18 mm | Stroke 25 … 100 mm | Linearity ±0.075 … ±0.2 % | Repeatability ±0.002 mm | 16 … 30 V | IP40
Voltage output converter with amplified current

Request a quote or technical information

Please tell us the quantity you need to measure, the range, the accuracy, the output signal, or any other requirements of your application.

We will help you select the right equipment and send you a quote or technical documentation.

You can also contact us by phone:

91 764 21 00

Shopping Basket